PROFIL SURJA HUBUNG KARENA PROSES ENERGIZED PADA SALURAN TRANSMISI 500 KV

- Yuniarto(1*)


(1) 
(*) Corresponding Author

Abstract


Transient over voltage that happened because switching surge have to be paid attention to don't cause the damage equipments of insulation coordination system. This research aim to perceive the transient over voltage at the end of 500 kv transmission line caused energized process by using EMTP (Electromagnetic Transients Program) as toll to simulate the energized process. Data for this research was taken from 500 kv transmission line Ungaran-Pedan. From this research was expected can become a reference for power company in planning insulation coordination at transmission line.

Result of research show that transient over voltage at the end of 500 kv transmission line caused energized process reach more or less twice its nominal voltage

Keywords : energized, karateristik, transient over voltage, EMTP


Full Text:

PDF

Article Metrics

Abstract view : 232 times
PDF - 69 times

DOI: https://doi.org/10.26714/me.v7i2.1367

Refbacks

  • There are currently no refbacks.




Copyright (c)



Editorial Office of Media Elektrika


Universitas Muhammadiyah Semarang FT-FMIPA Building, 7nd Floor. 
Department of Electrical Engineering
Jl. Kedungmundu Raya No. 18, Kota Semarang, Prov. Jawa Tengah, Indonesia 50273

Phone: 085299398663
Email: [email protected]

Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.