Audit Energi Listrik dan Analisis Peluang Penghematan pada Industri Es Kristal Bodas

Nur Achya Afifudin(1*), Ida Widihastuti(2)


(1) Fakultas Teknologi Industri, Universitas Islam Sultan Agung Semarang
(2) Fakultas Teknologi Industri, Universitas Islam Sultan Agung Semarang
(*) Corresponding Author

Abstract


This study aims to analyze electrical energy consumption and identify energy-saving opportunities in Bodas Crystal Ice Industry through an energy audit. The method applied is a quantitative descriptive energy audit involving historical consumption data, load measurements, and Specific Energy Consumption (SEC) analysis. The average electricity consumption was 6,253 kWh per month, of which ice production and refrigeration accounted for more than 95%. The initial SEC was 386 kWh/ton. After correcting the combined scenario to avoid double-counting freezer savings, the estimated consumption decreased to 4,852 kWh per month, equivalent to a 22.4% saving, while SEC decreased to 299.5 kWh/ton. These values represent technical-economic estimates that require verification after implementation.

 

Keywords: Energy Audit, Specific Energy Consumption, Ice Production Industry, Refrigeration System, Energy Saving


Keywords


Audit Energi, Konsumsi Energi Spesifik, Industri Es Kristal, Sistem Refrigerasi, Penghematan Energi

Full Text:

PDF

References


M. Habibah, R. R. Harahap, and B. Fachri, “Integrasi Sistem Penyimpanan Energi (Battery) Dengan Pengaturan Beban Otomatis Pada Gedung Cerdas,” J. Electr. Eng. Res., vol. 1, no. 1, pp. 33–39, 2025, [Online]. Available: https://raskhamedia.or.id

Khairul, D. Suseno, and Widodo, “Peran Audit Energi Dalam Pengembangan Program Manajemen Energi Di Bangunan Dan Industri: Sebuah Kajian Literatur,” RAMATEKNO, vol. 5, no. 2, pp. 133–140, 2025, [Online]. Available: https://ejournal.pei.ac.id/index.php/JRT1/article/view/285

G. A. Boyd, “Measuring plant level energy efficiency when production activities are not homogeneous: The ENERGY STAR energy performance indicator,” in Proceedings of the ACEEE Summer Study on Energy Efficiency in Industry, 2005, pp. 6–35.

T. Dunlop, “Energy efficiency: The evolution of a motherhood concept,” Soc. Stud. Sci., vol. 52, no. 5, pp. 710–732, 2022, doi: 10.1177/03063127221096171.

A. Fatoni and H. Setiawan, “Analisa Efisiensi Energi Pada Penggunaan Chiller Satu Kompresor Dan Dua Kompresor,” Sinergi, vol. 22, no. 2, 2024, doi: 10.31963/sinergi.v22i2.4829.

I. M. F. Nuryasa, A. Falah, and I. Sulistiyowati, “Monitoring Freon Pressure And Compressor Current Load To Maintain Efficient Internet Of Things (IoT)-Based Air Conditioning (AC) Performance,” Univ. Muhammadiyah Sidoarjo, 2026, doi: 10.21070/ups.9843.

A. W. Biantoro and D. S. Permana, “Analisis Audit Energi Untuk Pencapaian Efisiensi Energi Di Gedung Ab, Kabupaten Tangerang, Banten,” J. Tek. Mesin, vol. 6, no. Edisi Spesial, 2020, [Online]. Available: https://mercubuana.ac.id

I. W. Suriana, I. W. Sukadana, A. P. Abiyasa, and I. W. S. Yasa, “Audit Energi untuk Mengoptimalkan Penghematan Konsumsi Listrik di Kantor PT. Tunas Jaya Sanur,” Ranah Res. J. Multidiscip. Res. Dev., vol. 7, no. 4, pp. 2974–2985, 2025.

I. Faozan, “Analisis Perbandingan Evaporator Kulkas (Lemari Es) Dengan Mengunakan Refrigerant R-22 Dan R-134a,” J. Tek. Mesin, vol. 4, no. 3, p. 99, 2020, [Online]. Available: https://mercubuana.ac.id

M. Anwar, D. Sudrajat, Belyamin, and B. Wibowo, “Komparasi Konsumsi Daya Listrik Dan Efisiensi Energi Pada Modifikasi Freezer Kapasitas 100 L,” Indones. J. Fish. Sci. Technol., vol. 22, no. 1, pp. 37–43, 2026, doi: 10.14710/ijfst.22.1.37-43.

A. Lawrence, P. Thollander, M. Andrei, and M. Karlsson, “Specific Energy Consumption/Use (SEC) In Energy Management For Improving Energy Efficiency In Industry: Meaning, Usage And Differences,” Energies, vol. 12, no. 2, p. 247, 2019, doi: 10.3390/en12020247.

M. Hamid, S. Mengjie, T. Hadibi, M. Mohasan, D. A. Uglanov, and Z. Zekang, “Research progress and challenges in the preparation and application of ice-making technology,” Renew. Sustain. Energy Rev., vol. 223, 2025, doi: 10.1016/j.rser.2025.115996.


Article Metrics

Abstract view : 38 times
PDF - 6 times

DOI: https://doi.org/10.26714/me.v18i2.21152

Refbacks

  • There are currently no refbacks.




Copyright (c) 2026 MEDIA ELEKTRIKA



Editorial Office of Media Elektrika


Universitas Muhammadiyah Semarang FT-FMIPA Building, 7nd Floor. 
Department of Electrical Engineering
Jl. Kedungmundu Raya No. 18, Kota Semarang, Prov. Jawa Tengah, Indonesia 50273

Phone: 085327178613
Email: [email protected]

Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.