ANALISIS PENYETELAN PROTEKSI ARUS LEBIH PENYULANG CIMALAKA DI GARDU INDUK 70 kV SUMEDANG
(1) 
(2) 
(3) 
(*) Corresponding Author
Abstract
20 kV distribution of PLN is not free from distractions short circuit. Greatest short
circuit fault current occurs at 20 kV bus bar. This led to widespread outages as a result of the
major security operation.
The aim of this study was to identify the final interruption of short circuit current, short
circuit fault current to calculate and determine the values Over Current Relay (OCR) and
Ground Fault Relay (GFR).
This study purposed to calculate short circuit current. The subject of research is the
disturbances that occurred in Cimalaka feeders. The data required for this study were
obtained from the Area Manager Distribution of Bandung. The data is analyzed to determine
the magnitude of short circuit current and Over Current Relay (OCR) and Ground Fault
Relay (GFR) adjustment.
The results show the short circuit fault current at 0% distance from feeder is 2428,391
A and short circuit current for 3 phase is 2103,049 A short circuit fault current and the
second phase of 570,406 A short circuit fault current one phase to the ground. The difference
in the relay settings data from the field with the calculation results showed that the
differences are not too significant, so the ability of the relays is still good. Thus, the feeder
protection relays Cimalaka at 70 kV substation Sumedang still good and doesn’t need to be
reset.
Keywords: Over Current Relay
circuit fault current occurs at 20 kV bus bar. This led to widespread outages as a result of the
major security operation.
The aim of this study was to identify the final interruption of short circuit current, short
circuit fault current to calculate and determine the values Over Current Relay (OCR) and
Ground Fault Relay (GFR).
This study purposed to calculate short circuit current. The subject of research is the
disturbances that occurred in Cimalaka feeders. The data required for this study were
obtained from the Area Manager Distribution of Bandung. The data is analyzed to determine
the magnitude of short circuit current and Over Current Relay (OCR) and Ground Fault
Relay (GFR) adjustment.
The results show the short circuit fault current at 0% distance from feeder is 2428,391
A and short circuit current for 3 phase is 2103,049 A short circuit fault current and the
second phase of 570,406 A short circuit fault current one phase to the ground. The difference
in the relay settings data from the field with the calculation results showed that the
differences are not too significant, so the ability of the relays is still good. Thus, the feeder
protection relays Cimalaka at 70 kV substation Sumedang still good and doesn’t need to be
reset.
Keywords: Over Current Relay
Full Text:
PDFArticle Metrics
Abstract view : 712 timesPDF - 704 times
DOI: https://doi.org/10.26714/me.v5i2.641
Refbacks
- There are currently no refbacks.
Copyright (c)
Editorial Office of Media Elektrika
Universitas Muhammadiyah Semarang FT-FMIPA Building, 7nd Floor. Phone: 085299398663 |
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.